Fault diagnosis of power transformer using neuro-fuzzy model


Akgundogdu A., Gozutok A., Kilic N., Ucan O. N.

Istanbul University - Journal of Electrical and Electronics Engineering, cilt.8, sa.2, ss.699-706, 2008 (Scopus, TRDizin)

  • Yayın Türü: Makale / Tam Makale
  • Cilt numarası: 8 Sayı: 2
  • Basım Tarihi: 2008
  • Dergi Adı: Istanbul University - Journal of Electrical and Electronics Engineering
  • Derginin Tarandığı İndeksler: Scopus, TR DİZİN (ULAKBİM)
  • Sayfa Sayıları: ss.699-706
  • Anahtar Kelimeler: Anfis, Classification, Dissolved gas in oil analysis, Fault diagnosis, Neuro-fuzzy, Power transformer
  • İstanbul Üniversitesi-Cerrahpaşa Adresli: Hayır

Özet

In this study, we have presented Nruro-Fuzzy model for fault diagnosis of power transformer based on dissolved gas analysis (DGA). DGA is a very efficient tool for monitoring transformers in-service behavior to avoid catastrophic failures, costly outages and losses of production. Determination of the fault type with few key gases is a convenience for on-line gas-in-oil monitoring systems, used for detecting incipient faults. Three key gases Methane (CH 4), Ethylene (C2H4) and Acetylene (C 2H2) were chosen for this study. Neuro-Fuzzy is a reliable classification technique based on fuzzy and Artificial Neural Networks (ANN). Total accumulated amount of these gases were calculated and 100 percents (%) of each gas used as inputs of Neuro-Fuzzy. The output is one of the fault types PD, Dl, D2, Tl, T2, and T3. Classification accuracy has reached up to 76.0 %.